Subject:
Pedestrian Signal Conductor in Existing Conduit
Type:
Plan
Question
Date:
7/29/2026 2:16:37 PM
Plan sheet 9(3) calls out for a new bore going across NB 250 for the 10 EA pedestrian signal conductors, yet the plans call out for existing conduit to be used to cross SB 250 with the 13 EA pedestrian signal conductors. Has it been confirmed that the existing bore across SB 250 can handle 13 additional conductors to fit inside the conduit? That's a lot of conduit considering the existing signal conductor is within the existing bored conduit.
Answer
Date:
8/3/2026 4:33:33 PM
We will add 60' of 3" bored conduit to the contract and plan sheets. Addendum forthcoming.